2 oscillation damping, Oscillation damping, Commissioning – Lenze EVF9333−xV User Manual

Page 233

Advertising
background image

Commissioning

Optimising the operating behaviour

Oscillation damping

6

6.11

6.11.2

l

6.11−3

EDSVF9333V EN 6.2−04/2012

6.11.2

Oscillation damping

Suppressing no−load oscillations in case of:

ƒ Drives with different rated power of controller and motor, e. g. when

operating with high switching frequency and the power derating
involved.

ƒ Operation of higher−pole motors.

ƒ Operation of three−phase AC drives > 10 kW.

Compensation of resonances in the drive kit:

ƒ Certain asynchronous motors may show this behaviour above

1

/

3

of

the rated speed (

1

/

3

× n

n

). This may result in an unstable operation

(current and speed variations).

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0234 damp value

20

−100

{1 %}

100 Influence of the oscillation

damping, function block MCTRL

l

Minimising a tendency to
oscillation of the drive

l

Influences the tendency to
oscillation of the drive

l

When C0025 >1 and C0006 = 1,
C0234 is set to 0

^
8.2−25

^
8.2−48

C0235 damping

5

1

{1 ms}

600 Filter time of the oscillation

damping, function block MCTRL

l

Filter time for the internal
signal for oscillation damping

^
8.2−25

^
8.2−48

C0236 damp limit

0.2

0.0

{0.1 Hz}

20.0 Limit value of oscillation damping,

function block MCTRL

l

Limit value for the internal
signal of oscillation damping

Description

Advertising