Parameter setting

Parameter setting with the XT EMZ9371BC keypad
Loading a parameter set

7

7.2
7.2.5

l

7.2−6

EDSVF9333V EN 6.2−04/2012

7.2.5

Loading a parameter set

The keypad serves to load a saved parameter set into the main memory
when the controller is inhibited. After the controller is enabled, it operates
with the new parameters.

}

Danger!

ƒ

When a new parameter set is loaded, the controller is
reinitialised and acts as if it had been connected to the mains:
– System configurations and terminal assignments can be

changed. Make sure that your wiring and drive configuration
comply with the settings of the parameter set.

ƒ

Only use terminal X5/28 as source for the controller inhibit!
Otherwise the drive may start in an uncontrolled way when
switching over to another parameter set.

)

Note!

ƒ

After switching on the supply voltage, the controller always
loads parameter set 1 into the main memory.

ƒ

It is also possible to load other parameter sets into the main
memory via the digital inputs or bus commands.

Step

Key
sequence

Action

1.

Inhibit controller

Terminal X5/28 = LOW

2.

Load the saved parameter set
into the main memory

A

z y Z Y

Select the code C0002 "PAR LOAD" in the
menu "Load/Store"

B

V

Change to the parameter level
The active parameter set is displayed, e. g.
display "0" and "Load Default"
If you want to restore the delivery status,
proceed with D

Select the parameter set
to be loaded

C

z

Load parameter set 1:

ð Set "1" "Load PS1"
Load parameter set 2:

ð Set "2" "Load PS2"
Load parameter set 3:

ð Set "3" "Load PS3"
Load parameter set 4:

ð Set "4" "Load PS4"

D

T V

"RDY" goes off. The parameter set is loaded
completely into the main memory if "RDY"
is displayed again.

3.

Change to the code level

A

V

Display of the operating level

B

V

Display of C0002 "PAR LOAD"

4.

Enable controller

Terminal X5/28 = HIGH
The drive is running with the settings of
the loaded parameter set

Advertising
This manual is related to the following products: