5 system error messages, 1 general error messages, System error messages – Lenze EVF9333−xV User Manual

Page 455: General error messages, Troubleshooting and fault elimination, System error messages general error messages

Advertising
background image

Troubleshooting and fault elimination

System error messages

General error messages

9

9.5

9.5.1

l

9.5−1

EDSVF9333V EN 6.2−04/2012

9.5

System error messages

9.5.1

General error messages

)

Note!

In the case of a query via system bus (CAN), the fault messages
are represented as numbers (see first column of the table).

Fault message

Description

Cause

Remedy

No.

Display

−−−

−−−

No fault

0011

OC1

Overcurrent in motor cable
(I

a

> 2.25 x I

N

; Hardware

monitoring)

In the event of a short circuit

l

Search for the cause of the
short circuit.

l

Check the motor cable.

Capacitive charging current of the
motor cable is too high

Use motor cable which is shorter
or of lower capacitance

Too short acceleration or
deceleration times in proportion
to the load (C0012, C0013, C0105)

l

Increase the gain (P
component) of the Imax
controller (C0075).

l

Reduce integral−action time
(integral action component) of
the Imax controller (C0076)

The drive is connected to the
coasting machine. The coasting is
caused by a short−time pulse
inhibit, e.g. at

l

OU (overvoltage in the DC bus)

l

external or internal controller
inhibit

l

Activate flying restart circuit

l

Encoder error

l

Tracks during encoder
feedback of the motor speed
are interchanged

Check wiring of the encoder

DC−injection braking at high
speeds

l

See

^ 9.4−1

Missing mains phase

l

Check the connections and the
supply cable of the device

l

Check mains voltage

0012

OC2

Motor cable earth fault

One of the motor phases has
earth contact.

l

Search for cause of short
circuit.

l

Check motor cable.

0013

OC3

Overload during acceleration.

Too short acceleration or
deceleration times in proportion
to the load (C0012, C0013,
C0105).

l

Increase the gain (P
component) of the current
controller (C0075).

l

Reduce the reset time (integral
action component) of the I

max

controller (C0076).

l

Increase ramp times.

l

^ 9.4−2, "controller in clamp
operation (fault OC3)"

0015

OC5

I x t overload

l

Frequent and too long
acceleration with overcurrent

l

Continuous overload with
I

motor

> 1.05 x I

rx.

Check drive dimensioning.

0016

OC6

I

2

xt overload

l

Frequent and too long
acceleration processes with
motor overcurrent.

l

Permanent motor overload
with I

motor

>I

rmotor

Check drive dimensioning.