4 mounting in "cold plate" technique, Mounting in "cold plate" technique, Installing of the standard device – Lenze EVF9333−xV User Manual

Page 56

Advertising
background image

Installing of the standard device

Standard devices in the power range 0.37 ... 11 kW
Mounting in "cold plate" technique

4

4.1
4.1.4

l

4.1−4

EDSVF9333V EN 6.2−04/2012

4.1.4

Mounting in "cold plate" technique

)

Note!

All 9300 vector frequency inverters are approved according to
UL508C. To maintain the guaranteed features, controllers in
"cold plate" must be mounted by the user. For this reason, these
frequency inverters have the marking UR (instead of UL).

The drive controllers can be mounted in ˜cold plate˜ technique, e.g. on
collective coolers. For this purpose, the drive controllers of type EVF93xx−CV
must be used.

Required mounting material from the scope of supply:

Description

Use

EVF9321
EVF9322

EVF9323
EVF9324

EVF9325
EVF9326

Quantity

Fixing bracket

Drive controller fixing

2

2

2

Sheet metal screw
3.5 × 13 mm (DIN 7981)

Mounting of fixing
bracket to the drive
controller

6

6

6

The following points are important for safe and reliable operation of the
controller:

ƒ Good thermal connection to the cooler

– The contact surface between the collective cooler and the controller

must be at least as large as the cooling plate of the controller.

– Plane contact surface, max. deviation 0.05 mm.
– When attaching the collective cooler to the controller, make sure to

use all specified screw connections.

ƒ Observe the thermal resistance R

th

given in the table. The values are

valid for controller operation under rated conditions.

9300

Cooling path

Power to be dissipated

Heatsink − environment

Type

P

v

[W]

R

th

[K/W]

EVF9321−CV

24

1.45

EVF9322−CV

42

0.85

EVF9323−CV

61

0.57

EVF9324−CV

105

0.33

EVF9325−CV

180

0.19

EVF9326−CV

360

0.10

ƒ The rated data and the derating factors at increased temperature also

apply to the ambient temperature of the drive controllers.

ƒ Temperature at the cooling plate of the drive controller: max. 75 °C.

Requirements for collective
coolers

Ambient conditions