Commissioning

Adjusting the motor

Motor temperature monitoring with PTC or thermal contact

6

6.6

6.6.3

l

6.6−9

EDSVF9333V EN 6.2−04/2012

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0585 MONIT OH8

3

0

TRIP

Configuration of motor
temperature monitoring

l

Temperature monitoring via
PTC input (T1, T2)

^
6.6−8

See System
Manual
(extension)

2

Warning

3

Off

)

Note!

ƒ

In the Lenze setting the motor temperature monitoring is
switched off!

ƒ

If you work with several parameter sets, the monitoring must
be activated separately in each parameter set!

1. Connect the monitoring circuit of the motor to T1 and T2.

– With 1.6 k

W < R < 4 kW, the monitoring responds.

2. Set the controller reaction:

– C0585 = 3: Temperature monitoring of the motor is switched off.
– C0585 = 0: TRIP error message (display of keypad: OH8

a)

– C0585 = 2: Warning signal (display of keypad: OH8

e)

Connect the PTC input with a fixed resistor:

ƒ R > 4 k

W: The fault message OH8 must be activated.

ƒ R < 1 k

W: Fault message must not be activated.

Activation