5.2.10

Motor cable

ƒ The used motor cables must

– meet the requirements on site (e.g. EN 60204−1, UL),
– comply with the following voltage data: EN 0.6/1 kV, UL 600 V.

ƒ For shielded motor cables, only use cables with braid made of tinned or

nickel−plated copper. Shields made of steel braid are not suitable.
– The overlap rate of the braid must be at least 70 % with an overlap

angle of 90°.

ƒ Use low−capacitance motor cables:

Power class

Capacitance per unit length

Core/core

Core/shield

3 ... 11 kW

from 2.5 mm

2

£100 pF/m

£ 150 pF/m

15 ... 30 kW

£ 140 pF/m

£ 230 pF/m

45 ... 55 kW

£ 190 pF/m

£ 320 pF/m

75 ... 90 kW

£ 250 pF/m

£ 410 pF/m

ƒ Ensure that the motor cable is as short as possible to have a positive

effect on the drive behaviour.

ƒ In group drives (multiple motors on one controller), the resulting cable

length l

res

is the crucial factor:

I

res

[m]

+ (l

1

) l

2

) l

3

...

) l

i

)

@ i

Ǹ

l

x

Length of the individual motor cable

l

res

Resulting length of the motor cable

i

Number of individual motor cables

ƒ The "technical data" (chap. 3.1) provided for the motor cable length

must be observed.

Specification

Cable length