Commissioning – Lenze EVF9333−xV User Manual

Page 215

Advertising
background image

Commissioning

Operating mode

V/f characteristic control

6

6.8

6.8.1

l

6.8−5

EDSVF9333V EN 6.2−04/2012

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0016 Umin boost

0.00

0.00

{0.01 %}

100.00 U

min

boost (FCODE)

l

C0016 = 1 % corresponds to a
boost of 1 % of the rated motor
voltage (C0090)

l

Code is freely configurable

^
6.8−4

C0021 slipcomp

à

−20.00

{0.01 %}

20.00 Slip compensation

à

Change of C0086, C0087 or
C0089 sets C0021 to the
calculated rated slip of the
motor

l

When changing over to the
vector control mode, C0021 is
set to 0

^
6.11−1

^
8.2−25

^
8.2−48

C0090

s

Mot voltage

à

0

{1 V}

1000 Rated motor voltage

à

depending on C0086

l

Motor selection in C0086 sets
the corresponding rated motor
voltage in C0090

l

Change of C0090 sets C0086 =
0

^ 6.6−1

1. Select "V/f characteristic control" mode (C0006 = 5, factory

adjustment).

2. Select V/f characteristic (C0014) if necessary

3. Enter the data of the motor nameplate.

4. If required, you can set a base frequency in C0015 which differs from

the rated motor frequency (C0089).

Adjustment