Configuration, Code table – Lenze EVF9333−xV User Manual

Page 366

Advertising
background image

Configuration

Code table

8

8.5

l

8.5−18

EDSVF9333V EN 4.0−11/2007

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0168

Display of the fault messages in
the history buffer

l

Keypad: LECOM error number

See System
Manual
(extension)

1 Fail no. act

Active fault

2 Fail no. old1

Last fault

3 Fail no. old2

Second to last fault

4 Fail no. old3

Third last fault

5 Fail no. old4

Fourth−last fault

6 Fail no. old5

Fifth−last fault

7 Fail no. old6

Sixth−last fault

8 Fail no. old7

Last but six fault

C0169

Display in [s]

Displays at what time the fault
(C0168) has occurred since mains
connection (C0179)

l

If a fault is followed by another
fault for several times, only the
time of the last occurrence is
stored

1 Failtime act

Active fault

2 Failtime old1

Last fault

3 Failtime old2

Second to last fault

4 Failtime old3

Third last fault

5 Failtime old4

Fourth−last fault

6 Failtime old5

Fifth−last fault

7 Failtime old6

Sixth−last fault

8 Failtime old7

Last but six fault

C0170

Displays how many times the
fault (C0168) has occurred after
the last mains connection

1 Counter act

Active fault

2 Counter old1

Last fault

3 Counter old2

Second to last fault

4 Counter old3

Third last fault

5 Counter old4

Fourth−last fault

6 Counter old5

Fifth−last fault

7 Counter old6

Sixth−last fault

8 Counter old7

Last but six fault

C0173

s

UG limit

1

Adaptation of UG thresholds
Check during commissioning and
adapt, if necessary!
All controllers in the system must
have the same threshold!

See System
Manual
(extension)

Mains

LU

OU

0

< 400 V

285 V

770 ... 755 V

Device with or without brake
chopper

1

400 V

285 V

770 ... 755 V

2

460 V

328 V

770 ... 755 V

3

480 V

342 V

770 ... 755 V

Device without brake chopper

4

480 V

342 V

800 ... 785 V

Device with brake chopper

C0178 Op timer

{s}

Display only
Total time of the controller enable
(X5/28 = HIGH)

C0179 mainstimer

{s}

Display only
Total time of mains "ON"

Advertising