Flying restart circuit without protection against unexpected start−up
(C0142 = 3):

0

1

2

3

4



‚

ƒ

„

9300vec088

Fig. 8.2−17

Signal characteristic for automatic start with flying restart circuit (C0142 = 3)

0 Speed setpoint (e.g. AIN−OUT)

1 Actual speed value

2 Fault (e.g. DCTRL−FAIL = HIGH)

3 Pulse inhibit (e.g. DCTRL−IMP = HIGH)

4 Enable controller (e.g. X5/28 = HIGH)

 The motor rotates with setpoint

‚ A fault (e.g. mains failure, TRIP SET) activates a pulse inhibit c. The motor

coasts. After eliminating the fault (e.g. mains recovery, TRIP RESET) the pulse
inhibit is deactivated.

ƒ The flying restart circuit is active now and calculates the current motor

speed. If, after an OU message, the pulse inhibit is deactivated again, the
flying restart circuit is not started.

„ The motor is accelerated along the set acceleration ramp to the speed

setpoint and is being kept there