Wiring of the standard device – Lenze EVF9333−xV User Manual

Page 163

Advertising
background image

Wiring of the standard device

Wiring of digital frequency input / digital frequency output

5

5.11

l

5.11−1

EDSVF9333V EN 6.2−04/2012

5.11

Wiring of digital frequency input / digital frequency output

Installation material required from the scope of supply:

Description

Use

Quantity

Protective cover

Protection for unused Sub−D connections

4

Field

Digital frequency output X10

Connection at drive controller Connector: female, 9−pole, Sub−D

Pin assignment

Dependent on the selected basic configuration

Output frequency

0 ... 500 kHz

Signal

Two−track with inverse 5 V signals (RS422) and zero track

Load capacity

Max. 20 mA per channel
(up to 3 slave drives can be connected)

Special features

The "Enable" output signal at X10/8 switches to LOW if the
drive controller is not ready for operation (e.g. disconnected
from mains). This may trip SD3 monitoring on the slave drive.

Internal voltage source
(X10/4, X10/5)

DC 5 V / max. 50 mA
Total current at X9/4, X9/5 and X10/4, X10/5: max. 200 mA

Field

Digital frequency input X9

Connection at drive controller Connector: male, 9−pole, Sub−D

Input frequency

TTL level: 0 ... 500 kHz
HTL level: 0 ... 200 kHz

Signal

Two−track with inverse signals and zero track
Two−track without inverse signals and zero track (only for HTL
level)

Signal evaluation

Via code C0427

Current consumption

Max. 5 mA

Special features

With activated SD3 monitoring, TRIP or warning is tripped if
the "Lamp Control" input signal at X9/8 switches to LOW.
Due to this the drive controller may respond if the master
drive is not ready for operation.

Technical data

Advertising
This manual is related to the following products: