Control cables

ƒ Control cables must be shielded to minimise interference injections.

ƒ For lengths of 200 mm and more, use only shielded cables for analog

and digital inputs and outputs. Under 200 mm, unshielded but twisted
cables may be used.

ƒ Connect the shield correctly:

– The shield connections of the control cables must be at a distance of

at least 50 mm from the shield connections of the motor cables and
DC cables.

– Connect the shield of digital input and output cables at both ends.
– Connect the shield of analog input and output cables at one end (at

the drive controller).

ƒ To achieve an optimum shielding effect (in case of very long cables,

with high interference) one shield end of analog input and output
cables can be connected to PE potential via a capacitor (e.g.
10 nF/250 V) (see sketch).

9300vec043

Fig. 5.3−2

Shielding of long, analog control cables