Commissioning

Changing the assignment of the control terminals X5 and X6

Free configuration of digital input signals

6

6.5

6.5.1

l

6.5−1

EDSVF9333V EN 6.2−04/2012

6.5

Changing the assignment of the control terminals X5 and X6

}

Danger!

If you select a configuration in C0005, the signal assignment of
the inputs and outputs will be overwritten with the
corresponding basic assignment!

ƒ

Adapt the signal assignment to your wiring!

6.5.1

Free configuration of digital input signals

ƒ Internal digital signals can be freely linked with external digital signal

sources. This serves to establish a freely configurable control of the
drive controller.
– Digital inputs X5/E1 ... X5/E5

ƒ A signal source can be linked with several targets. Ensure reasonable

linkages for not activating functions that are mutually exclusive (e. g.
linking a digital input with quick stop and DC injection braking at the
same time).

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0114

0

High active

HIGH level is
active

Inversion of digital input signals at
X5, function block DIGIN

^
6.5−1

See System
Manual
(extension)

1

LOW active

LOW level is active

1 DIGIN1 pol

0

Terminal X5/E1

2 DIGIN2 pol

0

Terminal X5/E2

3 DIGIN3 pol

0

Terminal X5/E3

4 DIGIN4 pol

1

Terminal X5/E4

5 DIGIN5 pol

0

Terminal X5/E5

5 DIGIN6 (ST) pol

0

Terminal X5/ST

Description