Commissioning – Lenze EVF9333−xV User Manual

Page 232

Advertising
background image

Commissioning

Optimising the operating behaviour
Slip compensation

6

6.11
6.11.1

l

6.11−2

EDSVF9333V EN 6.2−04/2012

V/f characteristic control

The slip compensation (C0021) is automatically calculated from the rated
motor speed (C0087) and the rated motor frequency (C0089). The entered
slip constant [%] is the rated slip of the motor in [%] relating to the
synchronous speed of the motor.

ƒ Calculating the slip compensation and entering it into C0021:

s

+

n

rsyn

* n

r

n

rsyn

@ 100 %

n

rsyn

+

f

r

@ 60

p

E

Slip constant (C0021) [%]

n

rsyn

Synchronous motor speed [min

−1

]

n

r

Rated motor speed according to
motor nameplate [min

−1

]

f

r

Rated motor frequency according to
motor nameplate [Hz]

p

Number of motor pole pairs
(1, 2, 3, ...)

ƒ If required, the slip compensation can be adapted manually:

– If C0021 is set too high, the drive may get unstable.
– With cyclic load impulses (e. g. centrifugal pump) a smooth motor

characteristic is achieved by smaller values in C0021 (possibly
negative values)

– Parameterise C0078 (filter time for the slip compensation) if you

want to change the motor response time to load changes
(dynamic

« slow).

ƒ The actual speed is output as an analog signal (in [%] of n

max

(C0011))

to MCTRL−NACT.

)

Note!

When operating synchronous or reluctance motors, C0021 must
be set to 0.

Vector control

Use C0021 to change the influence of the rotor resistance (C0082)
proportionally:

ƒ Reduce the value in C0021 at an increasing speed (negative values)

ƒ Increase the value in C0021 at a decreasing speed

)

Note!

When setting the vector control mode, the slip compensation
(C0021) is automatically set to 0.0 %.

ƒ

When you switch back to the V/f characteristic control mode,
the slip compensation must be re−adapted.

Adjustment