Wiring of the standard device – Lenze EVF9333−xV User Manual

Page 114

Advertising
background image

Wiring of the standard device

Standard devices in the power range 0.37 ... 11 kW
Motor connection

5

5.4
5.4.6

l

5.4−12

EDSVF9333V EN 6.2−04/2012

)

Note!

ƒ

We recommend to use Lenze system cables for wiring.

ƒ

For self−made cables only use cables with shielded cores
twisted in pairs.

PE

U

V

W

T1 T2

+UG -UG

PES

PES

PE

M

3~

PES

PES

KTY

X8/5

X8/8

PES

X8

X9

X10

9300vec121

Fig. 5.4−7

Circuit diagram of motor connection with KTY thermal sensor at incremental
encoder input X8

Characteristics of the connection for motor temperature monitoring:

Pins X8/5, X8/8 of incremental encoder input (X8)

Connection

Linear KTY thermal sensor

Tripping point

l

Warning: Adjustable

l

Error (TRIP): Fixed at 150 °C

Notes

l

Monitoring is not active in the Lenze setting.

l

The KTY thermal sensor is monitored with regard to interruption
and short circuit.

Motor with KTY thermal
sensor

Advertising