Commissioning, Adjusting the motor entry of motor data – Lenze EVF9333−xV User Manual

Page 190

Advertising
background image

Commissioning

Adjusting the motor
Entry of motor data

6

6.6
6.6.1

l

6.6−2

EDSVF9333V EN 6.2−04/2012

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0090

s

Mot voltage

à

0

{1 V}

1000 Rated motor voltage

à

depending on C0086

l

Motor selection in C0086 sets
the corresponding rated motor
voltage in C0090

l

Change of C0090 sets C0086 =
0

^
6.6−1

C0091

s

Mot cos phi

à

0.50

{0.01 }

1.00 Motor cos

j

à

depending on C0086

l

Motor selection in C0086 sets
the corresponding motor cos

j

in C0091

l

Change of C0091 sets
C0086 = 0

^
6.6−1

Choose similar motor

in C0086 according to the

criteria circuit configuration

and rated motor power

Operating mode "87 Hz

delta connection”?

Does C0086 contain

the motor?

Enter motor nameplate data:
C0081 = 3 x P
C0087 = ( 3 - 1) n + n
C0088 = I
C0089 = 87 Hz
C0090 = U
C0091 = cos

r

0

r

r

r

Ц

Ц

j

D

D

Enter motor nameplate data:
C0081, C0087, C0088, C0089,
C0090, C0091

Start entry motor data

Entry motor data completed

Choose motor in C0086

yes

yes

no

no

9300vec096

Fig. 6.6−1

Sequence diagram for motor data entry

P

N

Rated motor power

n

0

Synchronous speed

n

N

Rated motor speed

I

N

D

Rated motor current for delta connection

U

N

D

Rated motor voltage for delta connection

Sequence of the motor data
entry