5 current limits, Current limits, Commissioning – Lenze EVF9333−xV User Manual

Page 201

Advertising
background image

Commissioning

Adjusting the motor

Current limits

6

6.6

6.6.5

l

6.6−13

EDSVF9333V EN 6.2−04/2012

6.6.5

Current limits

The controllers are provided with a current limit value control which
determines the dynamic behaviour under load. The resulting utilisation is
compared to the current limit value set under C0022 for motor load and
under C0023 for generator load. If the current limit values are exceeded, the
controller changes its dynamic behaviour.

Motor overload during acceleration:

The controller extends the acceleration ramp.

Generator overload during deceleration:

The controller extends the deceleration ramp.

With increasing load and constant speed:

ƒ When the current limit of the motor mode is reached:

– The controller reduces the speed up to 0 min

−1

.

– The controller cancels the change of the speed if the load falls below

the limit value again.

ƒ When the current limit in the generator mode is reached:

– The controller increases the speed up to the maximum speed

(C0011).

– The controller cancels the change of the speed if the load falls below

the limit value again.

ƒ If a sudden load is built up at the motor shaft (e. g. the drive is blocked),

the overcurrent disconnection can respond (fault message OCx).

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0022 IMAX CURRENT

à

0

{0.01 A}

− I

max

limit in motor mode

à

Depending on C0086

^
6.6−13

C0023 Imax gen.

à

0

{0.01 A}

− I

max

limit in generator mode

à

Depending on C0086

^
6.6−13

Description

Controller performance when
a limit value is reached