Installing of the standard device – Lenze EVF9333−xV User Manual

Page 71

Advertising
background image

Installing of the standard device

Standard devices in the power range of 55 kW

Thermally separated mounting (push−through technique)

4

4.4

4.4.3

l

4.4−3

EDSVF9333V EN 6.2−04/2012

4.4.3

Thermally separated mounting (push−through technique)

For mounting in push−through technique, the drive controller of type
EVF93xx−EV must be used. In addition, the mounting set EJ0010 for
push−through technique is required.

ƒ For thermally separated mounting you have to modify the fan module.

(

4.4−4)

d

2

d

2

d

2

d

b

g

e2

a

d

1

h

h

e3

c2

c3

c4

e

e1

L

a1

d

3

b

1

c1

9300vec174

Fig. 4.4−2

Dimensions for thermally separated mounting 55 kW

9300 vector

Dimensions [mm]

Type

a

a1

b

b1

c1

c2

c3

c4

d

d1

d2

d3

e

1)

e1

e2

e3

g

h

EVF9331−EV

373

340

543

591

45

137.5

217.5

310

525

45

145

81

285

163.5

185

66

7

9

1)

For a fieldbus module plugged onto X1, consider mounting space for connecting cables

9300 vector

Dimensions [mm]

Type

Width

Height

EVF9331−EV

320

515

Dimensions

Mounting cutout in control
cabinet

Advertising