Commissioning – Lenze EVF9333−xV User Manual

Page 238

Advertising
background image

Commissioning

Optimising the operating behaviour
Boost correction with V/f characteristic control

6

6.11
6.11.3

l

6.11−8

EDSVF9333V EN 6.2−04/2012

A motor connected to a controller has a rated motor voltage of 400 V
(C0090 = 400 V). The voltage boost U

min

is set to 2 % (C0016 = 2 %).

ƒ At a voltage boost of 2 % and a rated motor voltage of 400 V,

U

min

= 8 V.

The voltage boost U

min

is to be optimised via C0080:

6 × U

min

3 × U

min

0

0

0.5

0.99

C0080

0

9300vec141

Fig. 6.11−3

Influence of boost correction

0 Maximum correction value when the output frequency is 0 Hz

ƒ When C0080 = 0.5, the maximum correction value is:

3 × U

min

= 3 × 8 V = 24 V

ƒ The maximum voltage boost is:

U

min

+ correction value = 8 V + 24 V = 32 V

Example