Configuration

Function blocks

Internal motor control with vector control (MCTRL2)

8

8.2

8.2.7

l

8.2−67

EDSVF9333V EN 6.2−04/2012

Flying restart circuit with protection against unexpected start−up
(C0142 = 2):

0

1

2

3

4



‚

ƒ

„

9300vec087

Fig. 8.2−23

Signal characteristic for manual start with flying restart circuit (C0142 = 2)

0 Speed setpoint (e.g. AIN−OUT)

1 Actual speed value

2 Fault (e.g. DCTRL−FAIL = HIGH)

3 Pulse inhibit (e.g. DCTRL−IMP = HIGH)

4 Enable controller (e.g. X5/28 = HIGH)

 The motor rotates with setpoint

‚ A fault (e.g. mains failure, TRIP SET) activates a pulse inhibit c . The motor

coasts. After eliminating the fault (e.g. mains recovery, TRIP RESET) the pulse
inhibit remains active until the controller is enabled again (e.g. LOW−HIGH
edge at X5/28)
Important in case of an OU message: if the OU message is not pending
anymore, the pulse inhibit is deactivated.

ƒ The flying restart circuit is active now and determines the current motor

speed

„ The motor is accelerated along the set acceleration ramp to the speed

setpoint and is being kept there