Wiring of the standard device

Standard devices in the power range 0.37 ... 11 kW

Mains connection: Fuses and cable cross−sections

5

5.4

5.4.4

l

5.4−5

EDSVF9333V EN 6.2−04/2012

L1 L2 L3 +UG -UG

PE

L1, L2, L3
+U , -U

G

G

0.5...0.6 Nm
4.4...5.3 lb-in

2

0
1

9300std033

Fig. 5.4−3

Mains connection, DC supply for drive controllers 0.37 ... 11 kW

0 Mains cable

1 Shield sheet

Securely clamp mains cable with the lugs

2 Mains and DC bus connection

L1, L2, L3: Connection of mains cable
+U

G

, −U

G

: Connection of DC−bus components or connection of the controller

in the DC−bus system (see system manual)
Cable cross−sections up to 4 mm

2

: Use wire end ferrules for flexible cables

Cable cross−sections > 4 mm

2

: Use pin−end connectors

5.4.4

Mains connection: Fuses and cable cross−sections

Supply conditions

Range

Description

Fuses

l

Utilisation category: only gG/gL or gRL

Cables

Laying systems B2 and C: Use of PVC−insulated copper cables, conductor
temperature < 70 °C, ambient temperature < 40 °C, no bundling of the cables or
cores, three loaded cores. The data are recommendations. Other
dimensionings/laying systems are possible (e.g. in accordance with VDE 0298−4).

RCCB

l

Controllers can cause a DC current in the PE conductor. If a residual current
device (RCD) or a fault current monitoring unit (RCM) is used for protection in
the case of direct or indirect contact, only one RCD/RCM of the following type
can be used on the current supply side:
– Type B (universal−current sensitive) for connection to a three−phase system
– Type A (pulse−current sensitive) or type B (universal−current sensitive) for

connection to a 1−phase system

Alternatively another protective measure can be used, like for instance
isolation from the environment by means of double or reinforced insulation,
or isolation from the supply system by using a transformer.

l

Earth−leakage circuit breakers must only be installed between mains supply
and controller.

Observe all national and regional regulations!

Mains connection, DC supply

Installation in accordance
with EN 60204−1