Troubleshooting and fault elimination

Fault elimination
Behaviour in case of overvoltage in the DC bus (OU message)

9

9.4
9.4.3

l

9.4−4

EDSVF9333V EN 6.2−04/2012

U

DC

t

C0912

³

t < C0912

t = C0912



‚

0

1

IMP

9300vec142

Fig. 9.4−2

Influence of the delay time (C0912)



Switch−off threshold OU

‚

Switch−on threshold OU

0

The period of time between exceeding the switch−off threshold OU and
undershooting the switch−on threshold OU equals or is higher than the
delay time set in C0912.
After undershooting the switch−on threshold OU, the pulse inhibit is
deactivated.

1

The period of time between exceeding the switch−off threshold OU and
undershooting the switch−on threshold OU is lower than the delay time set
in C0912.
The pulse inhibit is deactivated after the delay time in C0912 has elapsed.

ƒ The delay time in [ms] is set under C0912. The Lenze setting can be

changed by the factor 0.5 ... 2.

Adjustment