Configuration – Lenze EVF9333−xV User Manual

Page 320

Advertising
background image

Configuration

Function blocks
Internal motor control with vector control (MCTRL2)

8

8.2
8.2.7

l

8.2−58

EDSVF9333V EN 6.2−04/2012

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0913

s

OV handling

0

Value of the motor current during
the flying restart process or after
an OU message

l

When C0913 = 1, the motor is
driven with reduced current to
the setpoint speed during the
flying restart process of after
an OU message.

l

The setting is only effective for
the drives EVF9326 ... EVF9333

^
8.2−25

^
8.2−48

0

inactive

Non−reduced motor current

1

active

Reduced motor current

ƒ The signal at input MCTRL−N−SET is the speed setpoint in [%] and

always refers to the maximum speed (C0011).

ƒ In the most basic configurations, MCTRL−N−SET is connected with the

function block NSET (speed setpoint conditioning).
– It is also possible to connect MCTRL−N−SET with any other analog

output signal of an FB.

ƒ The speed setpoint at MCTRL−N−SET is always limited to ±100 % of the

maximum speed n

max

(C0011).

ƒ The speed setpoint is converted into a frequency setpoint by the motor

control and is limited to a maximum output frequency depending on
the chopper frequency f

chop

.

Chopper frequency f

chop

Maximum output frequency

16 kHz

600Hz

8 kHz

300Hz

2/4 kHz

150Hz

Speed setpoint selection

Speed setpoint limitation