4 controller inhibit, Controller inhibit, Commissioning – Lenze EVF9333−xV User Manual

Page 181

Advertising
background image

Commissioning

Controller inhibit

6

6.4

l

6.4−1

EDSVF9333V EN 6.2−04/2012

6.4

Controller inhibit

If the controller inhibit is active, the power outputs are inhibited.

ƒ The drive coasts in zero−torque mode.

ƒ Status display of keypad: Pulse inhibit

c

ƒ Status display at the controller: The green LED is blinking.

}

Danger!

Do not use the "controller inhibit" function (DCTRL1−CINH) for
emergency−off. The controller inhibit only inhibits the power
outputs and does not disconnect the controller from the mains!
The drive could start again any time.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0040 Ctrl enable

0

Controller enable

l

Controller can only be enabled
if X5/28 = HIGH

^
6.4−1

0

Ctrl inhibit

Controller inhibited

1

Ctrl enable

Controller enabled

Via terminal X5/28:

ƒ A LOW level at the terminal inhibits the controller (cannot be inverted)

ƒ A HIGH level re−enables the controller

Via the keys of the keypad (if C0469 = 1):

ƒ

s inhibits the controller

ƒ

u re−enables the controller

Via code C0040:

ƒ C0040 = 0 inhibits the controller

ƒ C0040 = 1 re−enables the controller

)

Note!

ƒ

The sources for controller inhibit are ANDed, i.e. the drive only
restarts if the controller inhibit signals of all signal sources
have been eliminated.

ƒ

The restart starts with zero speed. If centrifugal masses are
still rotating, this can lead to an overcurrent.

Description