2 manual safety function check, Manual safety function check, Safety engineering – Lenze EVF9333−xV User Manual

Page 482

Advertising
background image

Safety engineering

Functional test
Manual safety function check

11

11.4
11.4.2

l

11.4−2

EDSVF9333V EN 6.2−04/2012

11.4.2

Manual safety function check

For the functional test, check both disconnecting paths separately.

1. disconnecting path: Pulse inhibit via safety relay K

SR

How to proceed during the test:

1. Alternately apply LOW and HIGH level to input X11/34 and check the

states given in the table below.

Specification

Correct status

Individual test

Input relay activation (X11/34)

Output feedback (X11/K31)

Pulse inhibit

LOW

HIGH

Pulse enable

HIGH

LOW

The individual tests are passed if the correct states given in the table result.

2. disconnecting path: Controller inihibit

Requirement for the test:

ƒ "Quickstop" (QSP) function deactivated

ƒ "Automatic DC injection brake" deactivated (C0019 = 0)

ƒ Pulses enabled by the safety relay K

SR

(X11/34 = HIGH)

How to proceed during the test:

1. Set controller inhibit (X5/28 = LOW).

2. Define a setpoint n

set

> 0.

3. Check that the motor is not rotating.

The individual test is passed if the motor does not rotate.

Functional test not passed

If an individual test results in an impermissible status, the functional test is
not passed.

ƒ The drive or machine has to be shut down immediately.

ƒ Commissioning is not permitted until the safety function operates

correctly.