Lenze EVF9333−xV User Manual

Page 34

Advertising
background image

Safety instructions

Safety instructions for the installation according to UL or UR

2

2.4

l

2.4−2

EDSVF9333V EN 6.2−04/2012

ƒ

EVF9330 … EVF9333:
– Suitable for use on a circuit capable of delivering not more

than 10000 rms symmetrical amperes, 480 V maximum,
when protected by fuses.

– Suitable for use on a circuit capable of delivering not more

than 50000 rms symmetrical amperes, 480 V maximum,
when protected by J, T or R class fuses.

– Maximum surrounding air temperature: 0 ... +50 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.