Commissioning

Parameter setting with the XT EMZ9371BC keypad

Commissioning example in vector control mode

6

6.3

6.3.2

l

6.3−5

EDSVF9333V EN 6.2−04/2012

6.3.2

Commissioning example in vector control mode

The example describes how to commission a speed control for the controller
with power−related three−phase asynchronous motor.

Switch−on sequence

Note

1.

Insert the keypad

2.

Ensure that the controller is inhibited after
switching on the mains

misc008

59

28

X5

}

Terminal X5/28 = LOW
(see chapter "Commissioning"

®"controller inhibit")

3.

Ensure that no external error is active

Terminal X5/E4 = HIGH

4.

Switch on

A

The control card is supplied via an external voltage:
Switch on the external DC 24 V supply voltage

ON

misc002

B

The control card is supplied via the internal voltage:
Switch on the mains. The controller provides the
DC 24 V supply.

5.

After approx. 2 s the controller is initialised and the
keypad is in the operating level and displays the
current speed (C0051)

9371BC004

d

A

B

b

c

0050

00

0.00 Hz

0 %

6.

Change to the "Terminal I/O" menu and configure
the function of the control terminals to adapt them
to your application.
Lenze setting: C0005 = 1000 (basic configuration
"speed control")

Use C0002 = 0 to restore the Lenze
setting
(see chapter "Commissioning"

®"Change assignment of the control
terminal X5 and X6")

7.

For quick commissioning select the menu "Short
setup"

d

A

B

b

c

p

SHPRG

Para

Code

Menu

4

2

Quick start

V / f q u i c k

9371BC007

The submenu "Setup vector" contains
the codes that are required for
commissioning a standard application.
The digital inputs are configured in the
Lenze setting:
X5/E1: Deactivate CW rotation/quick
stop
X5/E2: Deactivate CCW rotation/quick
stop
X5/E3: Activate fixed setpoint 1 (JOG1)
X5/E4: Set error message (TRIP SET)
X5/E5: Reset error message (TRIP
RESET)
(see chapter "Parameter setting")

A

Use

V to change to the menu level

B

Use

z z Z z to change to the menu "Short setup"

and then to the submenu "Setup vector"

C

Use

Z to change to the code level to parameterise

your drive

Y Z

y

z

T V
S U

d

A

B

b

c

p

SHPRG

Para

Code

Menu

0034

00

0

A I N 1 r a n g e

9371BC008

8.

Adapt the controller to the mains (C0173)
Lenze setting: 1 (400 V mains voltage)

9.

Only for the variants V060, V110, V270, V300 in the
power range of 110 ... 400 kW:
Adapt the brake transistor threshold (C0174)
Lenze setting: 3 (500 V mains voltage, 885 V brake
voltage)

See code table

10.

Enter the motor data

See motor nameplate and chapter
"Commissioning"

® "Adapt motor

data"

A

If you use a Lenze motor:
Select the motor type connected under C0086.

The data of the Lenze motors are saved
under C0086.

B

If you do not use a Lenze motor:
Enter the data of the motor nameplate

l

Rated motor power (C0081)
– Lenze setting: device−dependent

l

Rated motor speed (C0087)
– Lenze setting: device−dependent