Configuration, Code table – Lenze EVF9333−xV User Manual

Page 352

Advertising
background image

Configuration

Code table

8

8.5

l

8.5−4

EDSVF9333V EN 4.0−11/2007

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0018 fchop

6

Switching frequency of the
inverter

l

General rule: the lower the
switching frequency the
– lower the power loss
– higher the noise generation
– better the concentricity

factor

– Observe derating

information at high
switching frequencies

l

The max. output frequency
(f

out

) amounts to:

– f

chop

= 16 kHz

Þf

out

= 600 Hz

– f

chop

= 8 kHz

Þf

out

= 300 Hz

– f

chop

= 4 kHz

Þf

out

= 150 Hz

– f

chop

= 2 kHz

Þf

out

= 150 Hz

^ 6.9−1

0

auto chop

automatic
change−over of the
switching
frequency
between
16/8/2 kHz

1

2 kHz sin

optimised smooth
running

2

4 kHz f_top

power−optimised

3

8 kHz f_top

power−optimised

4

8 kHz sin

noise optimised

5

16 kHz sin

noise optimised

6

auto 8/2 kHz

noise /
power−optimised
with automatic
change−over to
low switching
frequency

C0019 Thresh nact=0

0

−36000

{1 rpm}

36000 Operating threshold − automatic

DC injection brake (Auto−GSB)

l

Falling below the threshold in
C0019 activates automatic DC
injection braking when the
holding time set under C0107 >
0

^
8.2−25

^
8.2−48

C0020 turn value

100

0

{1 %}

200 Influence on concentricity factor

l

Manual influence on the
concentricity factor of the
motor

C0021 slipcomp

à

−20.00

{0.01 %}

20.00 Slip compensation

à

Change of C0086, C0087 or
C0089 sets C0021 to the
calculated rated slip of the
motor

l

When changing over to the
vector control mode, C0021 is
set to 0

^
6.11−1

^
8.2−25

^
8.2−48

C0022 IMAX CURRENT

à

0

{0.01 A}

− I

max

limit in motor mode

à

Depending on C0086

^
6.6−13

C0023 Imax gen.

à

0

{0.01 A}

− I

max

limit in generator mode

à

Depending on C0086

^
6.6−13

C0025

s

Feedback type

1

Speed feedback

^ 6.7−1

1

no feedback

No feedback

100

IT (C420) − X8

Input of the
number of
increments in
C0420

Incremental encoder at X8

l

Incremental encoders with TTL
level can only be connected to
X8.

101

IT (C420) − X9

Input of the
number of
increments in
C0420

Incremental encoder at X9

l

Connect incremental encoders
with HTL−level on X9 only

Number of
increments:

Incremental encoder at X8

l

Incremental encoders with TTL
level can only be connected to
X8.

110

IT512−5V

512 inc

111

IT1024−5V

1024 inc

112

IT2048−5V

2048 inc

113

IT4096−5V

4096 inc

Advertising