Notes on project planning

Optimisation of the controller and mains load

5

5.2

5.2.7

l

5.2−5

EDSVF9333V EN 6.2−04/2012

5.2.7

Optimisation of the controller and mains load

A mains choke is an inductance which can be included in the mains cable of
the frequency inverter. As a result, the load of the supplying mains and the
controller is optimised:

ƒ Reduced system perturbation: The curved shape of the mains current

approaches a sinusoidal shape.

ƒ Reduced mains current: The effective mains current is reduced, i.e. the

mains, cable, and fuse loads are reduced.

ƒ Increased service life of the controller: The electrolytic capacitors in the

DC bus have a considerably increased service life due to the reduced AC
current load.

There are no restrictions for the combinations of mains chokes and RFI filters
and/or motor filters. Alternatively, a mains filter can be used (combination
of mains choke and RFI filter in a common housing).

)

Note!

ƒ

Some controllers must generally be operated with a mains
choke or a mains filter.

ƒ

If a mains choke or a mains filter is used, the maximum
possible output voltage does not reach the value of the mains
voltage (typical voltage drop at the rated point 4 ... 6 %).