Configuration – Lenze EVF9333−xV User Manual

Page 313

Advertising
background image

Configuration

Function blocks

Internal motor control with vector control (MCTRL2)

8

8.2

8.2.7

l

8.2−51

EDSVF9333V EN 6.2−04/2012

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0056 MCTRL−MSET2

−100.00

{0.01 %}

100.00 Read only. The output signal

depends on the operating mode:

l

Current motor current in case
of V/f characteristic control,
function block MCTRL1

l

Torque setpoint in case of
vector control, function block
MCTRL2

^
8.2−25

^
8.2−48

C0058 MCTRL−FACT

−600.0

{0.1 Hz}

600.0 Output frequency

l

Display only

l

MCTRL−FACT = 100.0 % =
1000.0 Hz

^
8.2−25

^
8.2−48

C0063 Mot temp

0

{1 °C}

200 Motor temperature

l

Read only

l

Monitoring of the motor
temperature must be
activated.

l

KTY at X8/5, X8/8:
– At 150 °C, TRIP OH3 is set
– Early warning is possible via

OH7, temperature is set in
C0121

l

PTC, thermal contact at T1, T2:
– Release sets TRIP or

warning OH8

^
8.2−25

^
8.2−48

C0064 Utilization

0

{1 %}

150 Device utilisation I×t

l

Read only

l

Device utilisation during the
last 180 s of operating time

l

C0064 > 100 % releases
warning OC5

l

C0064 > 140 % limits the
output current of the controller
to 67 % of the maximum
current in C0022

^
8.2−25

^
8.2−48

C0066 MOTOR LOAD

0

{1 %}

250 Motor load I

2

×t

^
8.2−25

^
8.2−48

C0070 Vp speed CTRL

10.0

0.0

{0.1 }

255.9 Gain of speed controller

^
8.2−25

^
8.2−48

C0071 Tn speed CTRL

50

1

{1 ms}

6000 Integral−action time of speed

controller
C0071 = 6000 ms: No
integral−action time

C0075 Vp curr CTRL

0.20

0.00

{0.01 }

0.99 Gain of current controller

l

Vector control: gain of current
controller

l

V/f characteristic control:
maximum current controller

^
8.2−25

^
8.2−48

C0076 Tn curr CTRL

10.0

0.1

{0.1 ms}

2000.0 Integral−action time of current

controller

l

Vector control: integral−action
time of current controller

l

V/f characteristic control:
maximum current controller

l

C0076 = 2000 ms: current
controller is switched off

^
8.2−25

^
8.2−48