Configuration – Lenze EVF9333−xV User Manual

Page 266

Advertising
background image

Configuration

Function blocks
Diameter calculator (DCALC)

8

8.2
8.2.1

l

8.2−4

EDSVF9333V EN 6.2−04/2012

In configurations with a speed forward control it is common to multiply the
precontrol signal with the reciprocal value of the diameter (d). This value is
output at DCALC1−OUT.

ƒ C1308 = 0: DCALC1−OUT = d

ƒ C1308 = 1: DCALC1−OUT = 1/d

For the conversion to 1/d the reference value for the diameter has to be
defined in C1309, for which the signal at DCALC1−OUT is to be 100 %.

ƒ Normally C1309 corresponds to the minimum diameter in C1305

(d

min

).

In order to ensure a continuous transition when setting new diameter
values, a ramp function generator is activated if C1310 > 0 s.

A window comparator compares the corresponding newly calculated value
to the value last filtered.

ƒ In C1311 the maximum difference in [%] between the two values is

defined.

ƒ DCALC1−I=0 is set to LOW if the maximum difference is exceeded.

Current diameter (C1328)

C1328 [mm]

+

DCALC1−N−LINE [inc]

DCALC1−N−WIND [inc]

@

C1300 [rpm]
C1301 [rpm]

@ C1304 [mm]

Output signal at DCALC1−OUT

For C1308 = 0 (DCALC1−OUT = d):

DCALC1−OUT [%]

+

C1328 [mm]
C1304 [mm]

@ 100 %

For C1308 = 1 (DCALC1−OUT = 1/d):

DCALC1−OUT [%]

+

C1304 [mm]
C1328 [mm]

@

C1309 [mm]
C1304 [mm]

@ 100 %

)

Note!

The value at DCALC1−OUT is limited by the maximum reel
diameter (C1306) and the minimum reel diameter (C1305).

Converting the diameter (d)
to 1/d

Web break monitoring

Formulas for calculation