Configuration, Code table – Lenze EVF9333−xV User Manual

Page 408

Advertising
background image

Configuration

Code table

8

8.5

l

8.5−60

EDSVF9333V EN 4.0−11/2007

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0912 OV delay time

à

{1 ms}

− Delay time of the pulse enable

after an OU message

à

Depending on C0082, C0086,
C0087, C0088, C0089, C0090,
C0091, C0092
A change of one of the codes
resets C0912 to the time of the
selected motor

l

The time is derived from the
double rotor time constant

^
8.2−25

^
8.2−48

^ 9.4−3

C0913

s

OV handling

0

Value of the motor current during
the flying restart process or after
an OU message

l

When C0913 = 1, the motor is
driven with reduced current to
the setpoint speed during the
flying restart process of after
an OU message.

l

The setting is only effective for
the drives EVF9326 ... EVF9333

^
8.2−25

^
8.2−48

0

inactive

Non−reduced motor current

1

active

Reduced motor current

C0940 Numerator

1

−32767

{1}

32767 Configuration of conversion factor

with numerator and denominator,
function block CONV1

See System
Manual
(extension)

C0941 Denominator

1

1

{1}

32767

OUT [%]

+ IN [%] @ C0940

C0941

C0942

s

CFG: IN

1000 FIXED0%

^ Selection list 1

Configuration of analog input
signal, function block CONV1

C0943 DIS: IN

−199.99

{0.01 %}

199.99 Function block CONV1

l

Display of the signal linked in
C0942

C0945 Numerator

1

−32767

{1}

32767 Configuration of conversion factor

with numerator and denominator,
function block CONV2

See System
Manual
(extension)

C0946 Denominator

1

1

{1}

32767

OUT [%]

+ IN [%] @ C0945

C0946

C0947

s

CFG: IN

1000 FIXED0%

^ Selection list 1

Configuration of analog input
signal, function block CONV2

C0948 DIS: IN

−199.99

{0.01 %}

199.99 Function block CONV2

l

Display of the signal linked in
C0947

C0950 Numerator

1

−32767

{1}

32767 Configuration of conversion factor

with numerator and denominator,
function block CONV3

See System
Manual
(extension)

C0951 Denominator

1

1

{1}

32767

OUT [%]

+ IN [rpm] @

100 %

15000 rpm

@ C0950

C0951

C0952

s

CFG: IN

1000 FIXED0%

^ Selection list 1

Configuration of analog input
signal, function block CONV3

C0953 DIS: IN

−199.99

{0.01 %}

199.99 Function block CONV3

l

Display of the signal linked in
C0952

C0955 Numerator

1

−32767

{1}

32767 Configuration of conversion factor

with numerator and denominator,
function block CONV4

See System
Manual
(extension)

C0956 Denominator

1

1

{1}

32767

OUT [%]

+ IN [rpm] @

100 %

15000 rpm

@ C0955

C0956

C0957

s

CFG: IN

1000 FIXED0%

^ Selection list 1

Configuration of analog input
signal, function block CONV4

C0958 DIS: IN

−199.99

{0.01 %}

199.99 Function block CONV4

l

Display of the signal linked in
C0957