Configuration
Function blocks
Internal motor control with vector control (MCTRL2)
8.2
8.2.7
l
8.2−53
EDSVF9333V EN 6.2−04/2012
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0091
s
Mot cos phi
à
0.50
{0.01 }
1.00 Motor cos
j
à
depending on C0086
l
Motor selection in C0086 sets
the corresponding motor cos
j
in C0091
l
Change of C0091 sets
C0086 = 0
^ 6.6−1
C0092
s
Mot Ls
à
0.0
{0.1 mH}
6500.0 Motor stator inductance
à
Value is evaluated by motor
parameter identification from
C0088, C0089, C0090 and
C0091
à
Selection of a motor in C0086
sets the corresponding stator
inductance value in C0092
^ 6.6−1
C0095
s
Mot Io
à
0.00
{0.01 A}
1000.00 Motor magnetising current
à
depending on C0086, C0088
and C0091
l
Change of C0086, C0088 and
C0091 sets C0095 to the Lenze
setting
l
Change of C0095 sets
C0086 = 0
^ 6.6−1
^
6.11−5
C0105 QSP Tif
5.00
0.00
{0.01 s}
999.90 Quick stop deceleration time
l
The deceleration time refers to
a speed variation of C0011 ... 0
^
8.2−25
^
8.2−48
C0107 holding time
0.00
0.00
{0.01 s}
9999.90 Hold time for automatic DC
injection braking (Auto−GSB)
^
8.2−25
^
8.2−48
C0132
s
Controller
enable fly
delay
à
0
{1 ms}
9999 Minimum time for controller
inhibit with active flying restart
circuit, delays the start of the
flying restart process after
controller enable
à
depending on C0082, C0086,
C0087, C0088, C0089, C0090,
C0091, C0092
A change of one of the codes
resets C0132 to the minimum
time of the selected motor
l
The time is derived from the
double rotor time constant
^
8.2−25
^
8.2−48