2 open and closed loop control, Open and closed loop control, Technical data – Lenze EVF9333−xV User Manual

Page 39

Advertising
background image

Technical data

Open and closed loop control

3

3.2

l

3.2−1

EDSVF9333V EN 6.2−04/2012

3.2

Open and closed loop control

Field

Values

Control methods

V/f characteristic control (linear, square), vector control

Switching frequency

1 kHz, 2 kHz or 4 kHz

Torque behaviour in case of vector
control

Maximum torque

1.5 × M

r

for 60 s if rated motor power = rated 9300 vector power

Setting range

to 1:10
(1 : 20 with feedback)

in the range of 6 ... 100 % f

r

Speed control without feedback

Min. mechanical motor frequency

1 % f

r

Torque 0 ... M

N

Setting range

1 : 100

relating to f

r

and M

r

Accuracy

± 0.5 % f

N

in the range of 6 ... 100 % f

N

Speed control without feedback

Min. mechanical motor frequency

0.1 % f

N

Torque 0 ... M

N

Setting range

1 : 1000

relating to f

r

and M

r

Accuracy

± 0.1 % of f

r

Output frequency

Field

− 300 Hz ... + 300 Hz

Absolute resolution

0.06 Hz

Standardised resolution

Parameter data: 0.01 %,
Process data: 0.006 % (= 2

14

)

Digital setpoint selection

Accuracy

± 0.005 Hz (= ± 100 ppm)

Analog setpoint selection

Linearity

± 0.15 %

signal level: 5 V or 10 V

Temperature sensitivity

± 0.1 %

0 ... 50 °C

Offset

± 0.1 %

Analog inputs/outputs

l

2 inputs (bipolar)

l

2 outputs (bipolar)

Digital inputs/outputs

l

6 inputs (freely assignable)

l

1 input for controller inhibit

l

4 outputs freely assignable)

l

1 incremental encoder input (500 kHz, TTL level); Design: 9−pole Sub−D socket

l

1 digital frequency input (500 kHz, TTL level or 200 kHz, HTL level); type: 9−pole Sub−D
socket; can be alternatively used as incremental encoder input (200 kHz, HTL level)

l

1 master frequency output (500 kHz, TTL level); Design: 9−pole Sub−D socket

Cycle times

Digital inputs

1 ms

Digital outputs

1 ms

Analog inputs

1 ms

Analog outputs

1 ms (smoothing time:

tt = 2 ms)

Operation in generator mode

Integrated brake transistor (optional)

f

r

rated motor frequency

M

r

rated motor torque