Wiring of the standard device
Standard devices in the power range 15 ... 30 kW
Mains connection: Fuses and cable cross−sections
5.5
5.5.4
l
5.5−6
EDSVF9333V EN 6.2−04/2012
Supply conditions
Range
Description
Fuses
l
Only according to UL 248
l
Mains short−circuit current up to 5000 A
rms
: All classes permissible
l
Mains short−circuit current up to 50000 A
rms
: Only classes "J", "T" or "R"
permissible
Cables
l
Only in accordance with UL
l
The cable cross−sections specified in the following apply under the following
conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C
Observe all national and regional regulations!
9300
Rated fuse current
Cable cross−section
Fuse
L1, L2, L3, PE
Type
[A]
[AWG]
Operation with mains choke/mains filter
EVF9327−xV
35
8
EVF9328−xV
50
6
EVF9329−xV
80
4
Installation to UL
Operation at rated power