Stretching factor

The stretching factor defines the ratio with which the drive is to run faster
or slower than the setpoint.

The setpoint at DFSET−IN is evaluated. The result is output to DFSET−POUT.

DFSET−POUT

+ DFSET−IN @ DFSET−VP−DIV

C0533

The stretching factor results from numerator and denominator.

ƒ The numerator (DFSET−VP−DIV) can be defined as a variable from the

analog signal source or as a fixed value from a code.

ƒ Enter the denominator under C0533.

)

Note!

When calculating the stretching factor, the input signal at
DFSET−VP−DIV is not processed in a scaled mode. A signal of
100 % corresponds to a count value of 16384.

Gearbox factor

The gearbox factor defines the ratio by means of which the drive speed can
be changed additionally.

The setpoint at DFSET−IN, multiplied by the stretching factor, is evaluated.
The result is output at DFSET−NOUT [in % of n

max

(C0011)].

DFSET−NOUT

+ DFSET−IN @ DFSET−VP−DIV

C0533

@ DFSET−RAT−DIV

C0033

The gearbox factor results from numerator and denominator.

ƒ The numerator (DFSET−RAT−DIV) can be defined as a variable from the

analog signal source or as a fixed value from a code.

ƒ Enter the denominator under C0033.

)

Note!

When calculating the gearbox factor, the input signal at
DFSET−RAT−DIV is not processed in a scaled mode. A signal of
100 % corresponds to a count value of 16384.

Setpoint conditioning with
stretching and gearbox factor