Wiring of the standard device – Lenze EVF9333−xV User Manual

Page 95

Advertising
background image

Wiring of the standard device

Notes on project planning

Motor cable

5

5.2

5.2.10

l

5.2−11

EDSVF9333V EN 6.2−04/2012

)

Note!

The cable cross−sections have been assigned to the permissible
current loading of the motor cables under the following
conditions:

ƒ

Compliance with IEC/EN 60204−1 for fixed cable installation

ƒ

Compliance with IEC 60354−2−52, table A.52−5 when using the
cable in a trailing cable

ƒ

Laying system C

ƒ

Ambient temperature 45 °C

ƒ

Continuous motor operation at a
– standstill current I

0

for servo motors or a

– rated current I

R

for three−phase asynchronous motors

The user is responsible for selecting a motor cable which
complies with the requirements of the current conditions if
different situations arise. Different situations may arise due to:

ƒ

Laws, standards, national and regional regulations

ƒ

Type of application

ƒ

Motor utilisation

ƒ

Ambient and operating conditions

ƒ

Laying system and bundling of cables

ƒ

Cable type

Motor cable

permanently installed for trailing cable

Cable cross−section

I

M

[A]

I

M

[A]

[mm

2

]

[AWG]

10.0

11.8

1.0

18

13.8

17.3

1.5

16

19.1

23.7

2.5

14

25.5

30.9

4.0

12

32.8

41.0

6.0

10

45.5

55.5

10

8

60.1

75.5

16

6

76.4

92.8

25

4

94.6

115

35

2

114

140

50

1

146

179

70

00

177

217

95

000

205

252

120

0000

)

Note!

Information on the design of the motor cable is provided in the
"System cables and system connectors" manual.

Cable cross−section

Advertising
This manual is related to the following products: