Chapter 6
Programming Overview

6–9

Specifying Indexed Addresses

The indexed address symbol is the # character, which is placed immediately
before the file-type identifier in a logical address. You can use more than
one indexed address in your ladder program.

When you specify indexed addresses, follow these guidelines:

Make sure the index value (positive or negative) does not cause the
indexed address to exceed the file type boundary.

When an instruction uses more than two indexed addresses, the controller
uses the same index value for each indexed address.

Set the index word to the offset value you want immediately before
enabling an instruction that uses an indexed address. The controller starts
operation at the base address plus the offset.

!

ATTENTION: Instructions with a # sign in an address
manipulate the offset value stored at S24. Make sure you
monitor or load the offset value you want prior to using an
indexed address. Otherwise unpredictable machine operation
could occur with possible damage to equipment and/or injury to
personnel.

Entering the # Character

When entering addresses, you can access the indexed address symbol by
pressing the key sequence shown below:

ANB

0

FUN

Example of Indexed Addressing

As an example, a Masked Move (MVM) instruction uses an indexed address
in the source and destination addresses. If the offset value is 10 (stored in
S24), the controller manipulates the data stored at the base address plus the
offset. See the table below.

Value:

Base Address:

Offset Value in

S24:

Offset Address:

Source

N10

10

N20

Destination

N50

10

N60