Type

Relay

MOSFET

Triac

Voltage

See Wiring Diagrams, p.

2–6.

Maximum
Load
Current

Refer to the
Relay Contact
Rating Table.

1.0A per point @ 55

°

C (131

°

F)

1.5A per point @ 30

°

C (86

°

F)

0.5A per point @ 55

°

C (131

°

F)

1.0A per point @ 30

°

C (86

°

F)

Minimum
Load
Current

10.0 mA

1 mA

10.0 mA

Current
per
Controller

1440 VA

3A for L16BBB
6A for L32BBB

1440 VA

Current
per
Common

8.0A

3A for L16BBB
6A for L32BBB

Not Applicable

Maximum
Off State
Leakage
Current

0 mA

1 mA

2 mA @ 132V ac
4.5 mA @ 264V ac

Off to On
Response

10 ms max.

0.1 ms

8.8 ms @ 60 Hz
10.6 ms @ 50 Hz

On to Off
Response

10 ms max.

1 ms

11.0 ms

Surge
Current
per Point

Not Applicable

4A for 10 ms

10A for 25 ms

Repeatability is once every 2 seconds at 55

°

C (131

°

F).

Relay Contact Rating Table (applies to all Bulletin 1761 controllers)

Maximum Volt

Amperes

mp r

Continuou

Voltamperes

Maximum Volts

Make

Break

Amperes Continuous

Make

Break

240V ac

7.5A

0.75A

2.5A

1800 VA

180 VA

120V ac

15A

1.5A

125V dc

0.22A

1.0A

28 VA

24V dc

1.2A

2.0A

28 VA

For dc voltage applications, the make/break ampere rating for relay contacts can be determined
by dividing 28 VA by the applied dc voltage. For example, 28 VA

÷

48V dc = 0.58A. For dc

voltage applications less than 48V, the make/break ratings for relay contacts cannot exceed 2A.
For dc voltage applications greater than 48V, the make/break ratings for relay contacts cannot
exceed 1A.