Chapter 14
Using High-Speed Counter Instructions

14–5

The table that follows uses the terminology shown here to indicate the status
of counting:

Up

– increments by 1 when the input energizes (edge).

Down

– decrements by 1 when the input energizes (edge).

Reset

– resets the accumulator to zero when the input energizes (edge).

Hold – disables the high-speed counter from counting while the input is
energized (level).

Count – increments or decrements by 1 when the input energizes (edge).

Direction – allows up counts when the input is de-energized and down
counts while the input is energized (level).

A – input pulse in an incremental (quadrature) encoder (edge/level)

B – input pulse in an incremental (quadrature) encoder (edge/level)

Z – reset pulse in an incremental (quadrature) encoder (edge/level)

– the signal is active on the rising edge only (off to on).

The table below lists the types of high-speed counter you can choose.

High-Sp d Count r T p

High-Sp d Count r Functionalit

Input Terminal Used

Pag

High-Speed Counter Type

High-Speed Counter Functionality

I/0

I/1

I/2

I/3

Page

Up

Up Counter operation uses a single-ended
input.

Up

Not Used

Not Used

Not Used

1

Up
(with external reset and hold)

Up Counter operation uses a single-ended
input with external reset and hold inputs.

Up

Not Used

Reset

Hold

14–5

Pulse and direction

Bidirectional operation uses both pulse
and direction inputs.

Count

Direction

Not Used

Not Used

Pulse and direction
(with external reset and hold)

Bidirectional operation uses both pulse
and direction inputs with external reset and
hold inputs.

Count

Direction

Reset

Hold

14–9

Up and down

Bidirectional operation uses both up and
down inputs.

Up

Down

Not Used

Not Used

Up and down
(with external reset and hold)

Bidirectional operation uses both up and
down pulse inputs with external reset and
hold inputs.

Up

Down

Reset

Hold

14–10

Encoder

Bidirectional operation uses quadrature
encoder inputs.

A

B

Not Used

Not Used

Encoder
(with external reset and hold)

Bidirectional operation uses both
quadrature encoder inputs with external
reset and hold inputs.

A

B

Z

Hold

14–12

One difference between Up Counters and Bidirectional Counters is that for
Bidirectional Counters the accumulator and preset values are not changed by
the high-speed counter when the presets are reached. The RAC and HSL
instructions must be used for this function. The Up Counters clear the
accumulator values and re-load the high preset values when the previous
preset is reached.