Or (or), Updates to arithmetic status bits, Entering the instruction – Rockwell Automation 1761-HHP-B30 MicroLogix 1000 with Hand-Held Programmer (HHP) User Manual
Page 202

Chapter 11
Using Data Handling Instructions
11–19
The value at source A is ORed bit by bit with the value at source B and then
stored in the destination. (This instruction differs from the OR input
instruction discussed in chapter 8.)
Truth Table
Dest = A OR B
A
B
Dest
0
0
0
1
0
1
0
1
1
1
1
1
Source A and B can either be a word address or a constant; however, both
sources cannot be a constant. The destination must be a word address.
Updates to Arithmetic Status Bits
With this Bit:
The Controller:
S0/0
Carry (C)
always resets.
S0/1
Overflow (V)
always resets.
S0/2
Zero (Z)
sets if result is zero; otherwise resets.
S0/3
Sign (S)
sets if result is negative (most significant bit is set)
otherwise resets.
Entering the Instruction
You enter the instruction from within the program monitor functional area.
P 0 0 0
O R
S R C A
2 5 5
P 0 0 0
O R
S R C B
N 0
1 0 0
P 0 0 0
O R
D E S T
N 0
1 0 0
OR
BITWISE INCLUS OR
Source A
255
Source B
N7:0
100
Dest
N7:0
100
Execution Times (
µ
sec) when:
True
False
33.68
6.78
Ladder representation:
Or (OR)
9
To enter the function code, press:
ENT
ANB
0
1
FUN