Chapter 11
Using Data Handling Instructions

11–27

P 0 0 0

F F L

S R C

N 1 0

0

P 0 0 0

F F L

F I F O

# N 1 2

0

P 0 0 0

F F L

R 0 0

L

3 4

P

9

P 0 0 0

F F U

F I F O

# N 1 2

0

P 0 0 0

F F U

D E S T

N 1 1

0

P 0 0 0

F F U

R 0 0

L

3 4

P

9

FFL Instruction

When rung conditions change from false-to-true, the controller sets the FFL
enable bit (EN). This loads the contents of the Source, N10, into the stack
structure indicated by the position number, 9. The position value then
increments.

The FFL instruction loads an element at each false-to-true transition of the
rung, until the stack is filled (34 elements). The controller then sets the done
bit (DN), inhibiting further loading.

FFU Instruction

When rung conditions change from false-to-true, the controller sets the FFU
enable bit (EU). This unloads the contents of the element at stack position 0
into the Destination, N11. All data in the stack is shifted one element toward
position zero and the highest numbered element is zeroed. The position
value then decrements.

The FFU instruction unloads an element at each false-to-true transition of the
rung, until the stack is empty. The controller then sets the empty bit (EM).

FFU instruction unloads

data from stack #N12 at

position 0, N12.

N12

0

N13

1

N14

2

3

4

5

6

7

8

9

33

34 words are
allocated for FIFO
stack starting at
N12, ending at N45.

FFL–FFU Instruction Pair

Loading and Unloading of Stack #N12

N10

N11

Position

Destination

Source

FFL instruction loads data

into stack #N12 at the next

available position, 9 in this

case.

N45

N15

N16

N17

N18

N19

N20

N21