The communication cable consists of a number of cable segments
daisy-chained together. The total length of the cable segments cannot exceed
1219 m (4000 ft).

When cutting cable segments, make them long enough to route them from
one AIC+ to the next with sufficient slack to prevent strain on the connector.
Allow enough extra cable to prevent chafing and kinking in the cable.

Use these instructions for wiring the Belden #3106A or #9842 cable. (If you
are using standard Allen-Bradley cables, see the Cable Selection Guide on
page 3–8.)

Connecting the Communication Cable to the DH-485 Connector

Important: A daisy-chained network is recommended. We do not

recommend the following:

Connector

Connector

Connector

Belden
#3106A or
#9842

Belden
#3106A or
#9842

Belden
#3106A or
#9842

Incorrect

Single Cable Connection

6 Termination
5

A

4

B

3 Common
2 Shield
1 Chassis Ground

White with Orange Stripes

Orange with White Stripes

Blue (#3106A) or
Blue with White Stripes (#9842)

Drain Wire

Shrink Tubing
Recommended

Multiple Cable Connection

to Successive Device

to Previous Device