Chapter 8
Using Basic Instructions

8–20

Use the RTO instruction to turn an output on or off after its timer has been on
for a preset time interval. The RTO instruction is a retentive instruction that
lets the timer stop and start without resetting the accumulated value (ACC).

The RTO instruction retains its accumulated value when any of the following
occurs:

Rung conditions become false.

You change controller operation from the RRUN, RCSN, or RSSN mode
to the RPRG mode.

The controller loses power.

A fault occurs.

Using Status Bits

This Bit

Is Set When

And Remains Set Until One

of the Following

Timer Done Bit DN (bit 13)

accumulated value is equal to
or greater than the preset value

the appropriate RES instruction
is enabled

Timer Timing Bit TT (bit 14)

rung conditions are true and
the accumulated value is less
than the preset value

rung conditions go false or
when the done bit is set

Timer Enable Bit EN (bit 15)

rung conditions are true

rung conditions go false

Important: To reset the retentive timer’s accumulated value and status bits

after the RTO rung goes false, you must program a reset (RES)
instruction with the same address in another rung.

Entering the Instruction

You enter the instruction from within the program monitor functional area.

P 0 0 0

R T O

A D D R

T 2

P 0 0 0

R T O

P R E

* * * 1 2 0

P 0 0 0

R T O

A C C

* * * * * 0

P 0 0 0

R T O

B A S E

0 . 0 1

S E C

(EN)

(DN)

RTO

RETENTIVE TIMER ON
Timer

T4:2

Time Base

0.01

Preset

120

Accum

0

Execution Times (

µ

sec) when:

True

False

38.34

27.49

Ladder representation:

Retentive Timer (RTO)

2

L

FUN

ENT

To enter the function code, press: