Chapter 15
Using Communication Protocols

15–4

EN ST DN ER EW NR TO Error Code

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

Reserved for Length (in elements)

Control Block Layout – CIF

Word

0

1

2

Offset Bytes

Not used

Not used

Not used

3

4

5

6

Node Number

Using Status Bits

Read/Write:

READ

ignore if timed out:

0

TO

Target Device:

SLC500/ML1000

to be retried:

0

NR

Control Block:

N7:0

awaiting execution:

0

EW

Local Destination File Address:

***

Target Node:

0

error:

0

ER

Target File Address:

***

message done:

0

DN

Message Length in elements

***

message transmitting:

0

ST

message enabled:

0

EN

control bit address:

N7:0/8

ERROR CODE: 0
Error Code Desc:

MSG Instruction Status Bits

The right column in the display above lists the various MSG instruction
status bits. These are explained below:

Time Out Bit TO (bit 08) Temporarily set this bit (1) to clear an
existing MSG instruction. This bit has no effect unless the ST bit has first
been set due to receiving an ACK (acknowlege). Your application must
supply its own timeout value. This bit is reset on any false-to-true rung
transition.

Negative Response Bit NR (bit 09) is set if the target processor is
responding to your message, but can not process the message at the
present time. The NR bit is reset at the next false-to-true MSG rung
transition that has a transmit buffer available. It is used to determine
when to send retries. The ER bit is also set at this time. Use this
feedback to initiate a retry of your message at a later time. This bit is
used with DH-485 protocol only.

Enabled and Waiting Bit EW (bit 10) is set on any false-to-true MSG
rung transition. This bit is reset when an ACK or NAK (no acknowledge)
is received, or on any true-to-false MSG rung transition.

Important: The operation of the EW bit has changed since Series C.

Error Bit ER (bit 12) is set when message transmission has failed. The
ER bit is reset the next time the rung goes from false to true.