Rockwell Automation 1761-HHP-B30 MicroLogix 1000 with Hand-Held Programmer (HHP) User Manual

Page 339

Advertising
background image

After You’ve Entered Your Program

Chapter 18

18–18

To change the function setting:

1. Put the controller in RPRG mode (if it is not already in that mode).

2. Access the program configuration menu.

3. Arrow up to the option

LOCK PROG

and select it.

2 times

ENT

L O C K

P R O G

Y E S

N O

4. Select the option

YES

and return to the home screen.

ENT

ESC

ESC

5. You must accept your program edits for this change to take affect. For

information on accepting edits, see the section that follows.

Important: You must cycle power on the MicroLogix 1000 HHP for

the lock to be enforced.

Changing the Version of Controllers that the Program Supports

The

CONTROL VERSION

option allows your program to access the

communication functions of Series C/D MicroLogix 1000 discrete
controllers.

Important: The control version function is only available when the Micro

Term is attached to a series C/D discrete controller containing a
series A/B program. It is not available when the Micro Term is
attached to an analog controller.

To change the default setting (

ML-A/B

):

1. Put the controller in RPRG mode (if it is not already in that mode).

2. Access the program configuration menu.