After You’ve Entered Your Program

Chapter 18

18–11

Selecting the Watchdog Scan

This byte value contains the number of 10 ms ticks allowed during a program
cycle. The default value is 10 (100 ms), but you can increase this to 255
(2.55 seconds) or decrease it to 1, as your application requires.

Important: If the watchdog value equals the current scan time value, a

watchdog major error will be declared (code 0022).

To change the setting:

1. Access the program configuration menu.

2. Arrow up to the option

WATCHDOG SCAN

and select it.

4 times

ENT

W A T C H D O G

S C A N

( x 1 0

m s )

1 0

3. Type in a new scan time.

4. Enter the setpoint and return to the home screen.

ENT

ESC

ESC