Rockwell Automation 1761-HHP-B30 MicroLogix 1000 with Hand-Held Programmer (HHP) User Manual

Page 319

Advertising
background image

Chapter 17
Entering and Editing Your Program

17–7

2. If this is the rung you want to delete, press

ENT

. If you do not want to

delete this rung, press

ESC

.

Important: If you delete a rung, you cannot undo the deletion.

Once the rung is deleted, the rung that immediately followed it in the
program file is displayed.

Deleting a Range of Rungs

Deleting a range of rungs uses the same key sequence required to delete a
single rung. Follow these steps to delete multiple rungs:

1. Start at the first or last rung of the range of rungs you want to delete.

2. While viewing any instruction located on that rung, press the key

sequence shown here:

FUN

DEL

A L L

D E L E T E

R U N G ( S ) :

x x x

The confirmation screen shown above appears. The number of the first
rung to be deleted is shown in the lower left-hand corner.

3. Press the key shown below to indicate you are deleting a range of rungs.

ORB

+ -

/

A dash appears on the screen.

4. Type in the number of the last rung to be deleted. This number can be

less than or greater than the first rung. The screen now looks like this:

D E L E T E

R U N G ( S ) :

x x x – x x x

5. Press

ENT

to delete the range of rungs. The rungs indicated and all the

rungs in between are deleted. To abort this procedure, press

ESC

.

Important: If you delete a range of rungs, you cannot undo the

deletion.

Once the range of rungs is deleted, the rung that immediately followed it in
the program file is displayed.

Advertising