Rockwell Automation 1761-HHP-B30 MicroLogix 1000 with Hand-Held Programmer (HHP) User Manual

Page 443

Advertising
background image

Appendix D
Understanding the Communication Protocols

D–17

MicroLogix Remote Packet Support

Series D MicroLogix discrete controllers and all MicroLogix analog
controllers can respond to communication packets (or commands) that do not
originate on the local DH-485 network. This is useful in installations where
communication is needed between the DH-485 and DH+ networks.

The example below shows how to send messages from a PLC device or a PC
on the DH+ network to a MicroLogix 1000 controller on the DH-485
network. This method uses an SLC 5/04 processor bridge connection.

When using this method:

PLC-5 devices can send read and write commands to MicroLogix
controllers.

MicroLogix 1000 controllers can respond to MSG instructions received.
The MicroLogix controllers cannot initiate MSG instructions to devices
on the DH+ network.

PC can send read and write commands to MicroLogix controllers.

PC can do remote programming of MicroLogix controllers.

DH

+

Network

PLC-5

SLC 5/04

Modular I/O Controller

DH-485 Network

MicroLogix 1000
Programmable
Controller

MicroLogix 1000
Programmable
Controller

MicroLogix 1000
Programmable
Controller

PLC-5

SLC 5/03 System

Advertising