Chapter 8
Using Basic Instructions

8–12

Entering the Instruction

You enter the instruction from within the program monitor functional area.

P 0 0 0

M P P

The example below illustrates when you would enter the MPP instruction.

NEW RUNG
LD a
OUT b

 MPS

AND c
OUT d

 MPP

OUT e

Instruction List

a

c

d

b

e





ANB and ORB are block connecting instructions. These instructions connect
two blocks of instructions in series or in parallel and produce an result that is
used in the remaining execution of the rung.

Using ANB

The ANB instruction is used to make a series connection of circuit blocks
with two or more contacts. (A series connection of circuit blocks with one
contact requires only an AND or ANI instruction. See page 16–1.)

Entering the Instruction

You enter the instruction from within the program monitor functional area.

P 0 0 0

A N B

1

To enter the function code, press:

FUN

ENT

2

L

And Block (ANB) and Or
Block (ORB)

0.40

ANB

0.40

ORB

] [

] [

] [

Execution Times (

µ

sec):

Ladder representation:

] [

] [

] [

] [

] [

ANB

ORB

ANB

0

To access the ANB instruction, press: