After You’ve Entered Your Program

Chapter 18

18–6

Setting the Start-Up Protection Bit

This selection allows you to check for, and attempt to recover from, major
errors before starting the first scan of your program.

When this bit is set to

NO

, the controller will fault if a major error occurs

while in RRUN, RCSN, or RSSN mode.

When this bit is set to

YES

and power is cycled when the controller starts in

RRUN mode, the controller executes the user-fault routine prior to the
execution of the first program scan. You can then clear the Major Error
Halted bit (S1/13) to resume operation in the RRUN mode.

If user-fault routine does not reset bit S1/13, the fault mode results.
Therefore, program the user-fault routine logic accordingly. When executing
the startup protection fault routine, the Major Error Fault (S6) will contain
the value 0016H.

To change the bit setting:

1. Put the controller in RPRG mode (if it is not already in that mode).

2. Access the program configuration menu.

3. Arrow down to the option

START PROTECT

and select it.

ENT

4 times

S T A R T

P R O T E C T

Y E S

N O

4. Select the option

YES

and return to the home screen.

ENT

ESC

ESC

5. You must accept your program edits for this change to take affect. For

information on accepting edits, see page 18–21.